Configuring Responder/Smart Grid
Network Adapter - Create Feature Classes

Version: 10.1

Resource Center Home

Network Adapter uses the following feature classes and tables when exporting to DMS. Some classes and attributes were added during Feeder Manager configuration. Some attributes were NOT added earlier and must be added. Ensure the following feature and object classes exist in your database with the displayed attributes and assigned domains before continuing to the next step.

Fields required by DMS are indicated in bold. Note that - with the exception of the CatalogID field - these fields must exist AND be populated with a valid value. The CatalogID field will be populated with a default value if it is Null.

Feature class and field names are displayed as they appear in the standard data models (Electric Distribution/MultiSpeak).

 

BreakerUnit/DynamicProtectiveDeviceUnit 

If your geodatabase does not include a BreakerUnit table, you will need to add the PhaseDesignation/PhasingCode and CatalogID fields to the CircuitSource/Source table.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

ScadaControlID/ScadaControlID

text (length=20)

 

 

CapacitorUnit/CapacitorUnit

Object table.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

Kvar/Kvar

long integer

Capacitor Unit KVAR

 

CircuitSource/Source

Object table.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

ID/FeederID

text (length=20)

 

Name/FeederName

text (length=20)

 

*CatalogID/CatalogID

text

 

*PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

ConnectionConfiguration/ConnectionConfiguration

text (length=5)

Circuit Source Connection Configuration

SubstationID/SubstationName

text (length=20)

 

* The CatalogID and PhaseDesignation/PhasingCode fields are required only if the geodatabase does not include a BreakerUnit or DynamicProtectiveDeviceUnit table.

 

ConductorInfo/ConductorInfo

Object table.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

ConductorMaterial/CondMatl

text

 

ConductorSize/CondSize

text

Conductor Size

 

DynamicProtectiveDevice/DynamicProtectiveDeviceBank

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FacilityID/FacilityID

text (length=20)

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

MaxContinuousCurrent/MaxContAmp

double

 

NormalPosition_A/PosA

long integer

Normal Status

NormalPosition_B/PosB

long integer

Normal Status

NormalPosition_C/PosC

long integer

Normal Status

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

ScadaControlID/ScadaControlID

text

 

SubtypeCD/SubtypeCode

long integer

 

SubstationID/SubstationID

text (length=50)

 

*BayID/BayID

text (length=50)

*Add this field if the device can act as a port to a switching facility. 

 

Fuse/FuseBank

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FacilityID/FacilityID

text (length=20)

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

NormalPosition_A/PosA

long integer

Normal Status

NormalPosition_B/PosB

long integer

Normal Status

NormalPosition_C/PosC

long integer

Normal Status

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

SubstationID/SubstationID

text (length=50)

 

*BayID/BayID

text (length=50)

 

*Add this field if the device can act as a port to a switching facility. 

 

FuseUnit/FuseUnit Object Class

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

LinkRating/LinkRtg

long integer

Fuse Link Rating

LinkType/FuseType

text (length=5)

Fuse Link Type

 

MiscNetworkFeature/MiscellaneousFeature

Only the FaultIndicator subtype is exported from the MiscNetworkFeature class. All other MiscNetworkFeatures are not exported.

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

FeederID/FeederID

text (length=20)

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

Direction/Direction

text (length=50)

FaultIndicatorDirection

SubtypeCD/SubtypeCode

long integer

 

 

PFCorrectingEquipment/CapacitorBank

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

BankKvar/BankKvar

text

 

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FacilityID/FacilityID

text (length=20)

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

 

Primary Conductors (PriOHElectricLineSegment, PriUGElectricLineSegment, BusBar, PrimaryOHLineSection, PrimaryUGLineSection)

Complex Edge Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

Length/Length

double

 

*NeutralMaterial/NeutType

text (length=5)

Neutral Material

*NeutralSize/NeutSize

text (length=5)

Neutral Size

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

OperatingVoltage/OperVolt

long integer

Electric Line Voltage

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

* Not on BusBar class

 

RecloserUnit/DynamicProtectiveDeviceUnit 

Object table.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

 

SectionalizerUnit/DynamicProtectiveDeviceUnit

Object table.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

 

ServicePoint/ServiceLocation

Network Adapter exports only ServicePoints that are connected to Conductors that have been configured to be exported. ServicePoints connected to secondary conductors are not exported unless the secondary is exported.

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

ConsumptionType/ ConsumptionType

text

Consumption Type

FeederID/FeederID

text (length=20)

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

LocationID/LocationID

text (length=20)

 

 

Substation/Substation

Simple point feature class that does not participate in the geometric network. 

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

SubstationID/SubstationID

text (length=50)

 

 

SwitchingFacility/SwitchingFacility  (optional)

Simple point feature class that does not participate in the geometric network. 

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

SubstationID/SubstationID

text (length=50)

 

  

Switch/SwitchBank

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FacilityID/FacilityID

text (length=20)

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

MaxContinuousCurrent/MaxContAmp

double

 

NormalPosition_A/PosA

long integer

Normal Status

NormalPosition_B/PosB

long integer

Normal Status

NormalPosition_C/PosC

long integer

Normal Status

ScadaControlID/ScadaControlID

text

 

SubtypeCD/SubtypeCode

long integer

 

SubstationID/SubstationID

text (length=50)

 

*BayID/BayID

text (length=50)

 

*Add this field if the device can act as a port to a switching facility.  

 

SwitchUnit/SwitchUnit Object Class

Object class.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

 

Transformer/TransformerBank

Simple Junction Feature that participates in the geometric network.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

ConsumptionType/ConsumptionType

text

Consumption Type

*HighSideConfiguration

text (length=5)

Transformer Bank High Side Configuration (Default = D-D)

HighSideProtection/PriProt

text (length=5)

Transformer Bank High Side Protection (Default = none)

*LowSideConfiguration

text (length=5)

Transformer Bank Low Side Configuration (Default = D-D)

LowSideVoltage/SecVolt

long integer

 

Owner/Owner

long integer

Owner (Default = 1:Company)

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FacilityID/FacilityID

text (length=20)

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

LowSideGroundResistance/ LowSideGroundResistance

double

 

OperatingVoltage/OperVolt

long integer

Electric Device Operating Voltage

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

Priority/Priority

long integer

Priority

**WindingCode

 

Winding Code

***TapChangerEquipment/TapChangerEquipment

 

 

*The HighsideConfiguration and LowSideConfiguration fields are necessary only if you are using an Electric Distribution data model.

**The WindingCode field is necessary only if you are using a MultiSpeak data model.

*** You can have a single TapChangerEquipment field with the TAPCHANGEREQUIPMENT field model name assigned. Alternately, you can assign the field model name to multiple fields that are concatenated to create a single tap changer ID. For the fields to be concatenated in a specific order, add a numerical suffice to the field model names (e.g., TAPCHANGEREQUIPMENT1, TAPCHANGEREQUIPMENT2) and assign them to the fields in the order to concatenate them.  

 

TransformerUnit/TransformerUnit Object Class

Object class.

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

CatalogID/CatalogID

text

 

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

RatedKVA

long integer

Transformer Unit KVA

 

VoltageRegulatorBank/RegulatorBank

Simple Junction Feature that participates in the geometric network. 

Field (Electric Distribution/MultiSpeak)

Data Type

Domain

ConsumptionType/ConsumptionType

text

Consumption Type

*HighSideConfiguration

text (length=5)

Transformer Bank High Side Configuration (Default = D-D)

HighSideProtection/PriProt

text (length=5)

Transformer Bank High Side Protection (Default = none)

*LowSideConfiguration

text (length=5)

Transformer Bank Low Side Configuration (Default = D-D)

Owner/Owner

long integer

Owner (Default = 1:Company)

ElectricTraceWeight/ElectricTraceWeight

long integer

 

FacilityID/FacilityID

text (length=20)

 

FeederID/FeederID

text (length=20)

 

FeederID2/FeederID2

text (length=20)

 

FeederInfo/FeederInfo

long integer

 

LowSideGroundResistance/ LowSideGroundResistance

double

 

OperatingVoltage/OperVolt

long integer

Electric Device Operating Voltage

PhaseDesignation/PhasingCode

long integer

Phase Designation (no default value)

Priority/Priority

long integer

Priority

***TapChangerEquipment/TapChangerEquipment

 

 

**WindingCode

 Text (length=50)

Winding Code

*The HighsideConfiguration and LowSideConfiguration fields are necessary only if you are using an Electric Distribution data model.

**The WindingCode field is necessary only if you are using a MultiSpeak data model.

*** You can have a single TapChangerEquipment field with the TAPCHANGEREQUIPMENT field model name assigned. Alternately, you can assign the field model name to multiple fields that are concatenated to create a single tap changer ID. For the fields to be concatenated in a specific order, add a numerical suffice to the field model names (e.g., TAPCHANGEREQUIPMENT1, TAPCHANGEREQUIPMENT2) and assign them to the fields in the order to concatenate them.  


Send Comment to documentation@schneider-electric.com