Using Responder
Reprocess Devices

Version: 10.2.1c and 10.2.1c SP3

Resource Center Home

In some circumstances, an incident in Responder may indicate a problem with your GIS data rather than an actual outage. Adding or removing customers, editing GIS data after incident creation, or errors in your data could all cause an incident to be outdated or incorrect. Running the Reprocess Devices tool for the incident after data corrections will perform incident device management (IDM) on all devices for the targeted incident. Responder will add or remove loadpoints for the incident and update outage times.

This tool will move loadpoint outage times back when necessary, for instance if a time is erroneously in the future ahead of an operation time of an upstream device, but it will not move loadpoint outage times forward as it needs to respect downstream, rolled-up loadpoints that could have been out at earlier times (based on other devices that may not be part of this incident).

This tool is available on the right-click utility menu for an incident under the following conditions:

 

 


Send Comment to ArcFMdocumentation@schneider-electric.com