Version: 10.2.1c and 10.2.1c SP3 |
Smart Grid Applications Overview > Network Adapter > Network Adapter for Multispeak > Network Adapter - Create Feature Classes |
Network Adapter uses the following feature classes and tables when exporting to DMS. Some classes and attributes were added during Feeder Manager configuration. Some attributes were NOT added earlier and must be added. Ensure the following feature and object classes exist in your database with the displayed attributes and assigned domains before continuing to the next step.
Fields required by DMS are indicated in bold. Note that - with the exception of the CatalogID field - these fields must exist AND be populated with a valid value. The CatalogID field will be populated with a default value if it is Null.
Feature class and field names are displayed as they appear in the standard data models (Electric Distribution/MultiSpeak).
BreakerUnit/DynamicProtectiveDeviceUnit
If your geodatabase does not include a BreakerUnit table, you will need to add the PhaseDesignation/PhasingCode and CatalogID fields to the CircuitSource/Source table.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
ScadaControlID/ScadaControlID |
text (length=20) |
|
CapacitorUnit/CapacitorUnit
Object table.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
Kvar/Kvar |
long integer |
Capacitor Unit KVAR |
CircuitSource/Source
Object table.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
ID/FeederID |
text (length=20) |
|
Name/FeederName |
text (length=20) |
|
*CatalogID/CatalogID |
text |
|
*PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
ConnectionConfiguration/ConnectionConfiguration |
text (length=5) |
Circuit Source Connection Configuration |
SubstationID/SubstationName |
text (length=20) |
|
* The CatalogID and PhaseDesignation/PhasingCode fields are required only if the geodatabase does not include a BreakerUnit or DynamicProtectiveDeviceUnit table.
ConductorInfo/ConductorInfo
Object table.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
ConductorMaterial/CondMatl |
text |
|
ConductorSize/CondSize |
text |
Conductor Size |
DynamicProtectiveDevice/DynamicProtectiveDeviceBank
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FacilityID/FacilityID |
text (length=20) |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
MaxContinuousCurrent/MaxContAmp |
double |
|
NormalPosition_A/PosA |
long integer |
Normal Status |
NormalPosition_B/PosB |
long integer |
Normal Status |
NormalPosition_C/PosC |
long integer |
Normal Status |
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
ScadaControlID/ScadaControlID |
text |
|
SubtypeCD/SubtypeCode |
long integer |
|
SubstationID/SubstationID |
text (length=50) |
|
*BayID/BayID |
text (length=50) |
*Add this field if the device can act as a port to a switching facility.
Fuse/FuseBank
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FacilityID/FacilityID |
text (length=20) |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
NormalPosition_A/PosA |
long integer |
Normal Status |
NormalPosition_B/PosB |
long integer |
Normal Status |
NormalPosition_C/PosC |
long integer |
Normal Status |
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
SubstationID/SubstationID |
text (length=50) |
|
*BayID/BayID |
text (length=50) |
|
*Add this field if the device can act as a port to a switching facility.
FuseUnit/FuseUnit Object Class
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
LinkRating/LinkRtg |
long integer |
Fuse Link Rating |
LinkType/FuseType |
text (length=5) |
Fuse Link Type |
MiscNetworkFeature/MiscellaneousFeature
Only the FaultIndicator subtype is exported from the MiscNetworkFeature class. All other MiscNetworkFeatures are not exported.
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
FeederID/FeederID |
text (length=20) |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
Direction/Direction |
text (length=50) |
FaultIndicatorDirection |
SubtypeCD/SubtypeCode |
long integer |
|
PFCorrectingEquipment/CapacitorBank
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
BankKvar/BankKvar |
text |
|
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FacilityID/FacilityID |
text (length=20) |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
Primary Conductors (PriOHElectricLineSegment, PriUGElectricLineSegment, BusBar, PrimaryOHLineSection, PrimaryUGLineSection)
Complex Edge Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
Length/Length |
double |
|
*NeutralMaterial/NeutType |
text (length=5) |
Neutral Material |
*NeutralSize/NeutSize |
text (length=5) |
Neutral Size |
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
OperatingVoltage/OperVolt |
long integer |
Electric Line Voltage |
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
* Not on BusBar class
RecloserUnit/DynamicProtectiveDeviceUnit
Object table.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
SectionalizerUnit/DynamicProtectiveDeviceUnit
Object table.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
ServicePoint/ServiceLocation
Network Adapter exports only ServicePoints that are connected to Conductors that have been configured to be exported. ServicePoints connected to secondary conductors are not exported unless the secondary is exported.
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
ConsumptionType/ ConsumptionType |
text |
Consumption Type |
FeederID/FeederID |
text (length=20) |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
LocationID/LocationID |
text (length=20) |
|
Substation/Substation
Simple point feature class that does not participate in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
SubstationID/SubstationID |
text (length=50) |
|
SwitchingFacility/SwitchingFacility (optional)
Simple point feature class that does not participate in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
SubstationID/SubstationID |
text (length=50) |
|
Switch/SwitchBank
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FacilityID/FacilityID |
text (length=20) |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
MaxContinuousCurrent/MaxContAmp |
double |
|
NormalPosition_A/PosA |
long integer |
Normal Status |
NormalPosition_B/PosB |
long integer |
Normal Status |
NormalPosition_C/PosC |
long integer |
Normal Status |
ScadaControlID/ScadaControlID |
text |
|
SubtypeCD/SubtypeCode |
long integer |
|
SubstationID/SubstationID |
text (length=50) |
|
*BayID/BayID |
text (length=50) |
|
*Add this field if the device can act as a port to a switching facility.
SwitchUnit/SwitchUnit Object Class
Object class.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
Transformer/TransformerBank
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
ConsumptionType/ConsumptionType |
text |
Consumption Type |
*HighSideConfiguration |
text (length=5) |
Transformer Bank High Side Configuration (Default = D-D) |
HighSideProtection/PriProt |
text (length=5) |
Transformer Bank High Side Protection (Default = none) |
*LowSideConfiguration |
text (length=5) |
Transformer Bank Low Side Configuration (Default = D-D) |
LowSideVoltage/SecVolt |
long integer |
|
Owner/Owner |
long integer |
Owner (Default = 1:Company) |
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FacilityID/FacilityID |
text (length=20) |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
LowSideGroundResistance/ LowSideGroundResistance |
double |
|
OperatingVoltage/OperVolt |
long integer |
Electric Device Operating Voltage |
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
Priority/Priority |
long integer |
Priority |
**WindingCode |
|
Winding Code |
***TapChangerEquipment/TapChangerEquipment |
|
|
*The HighsideConfiguration and LowSideConfiguration fields are necessary only if you are using an Electric Distribution data model.
**The WindingCode field is necessary only if you are using a MultiSpeak data model.
*** You can have a single TapChangerEquipment field with the TAPCHANGEREQUIPMENT field model name assigned. Alternately, you can assign the field model name to multiple fields that are concatenated to create a single tap changer ID. For the fields to be concatenated in a specific order, add a numerical suffice to the field model names (e.g., TAPCHANGEREQUIPMENT1, TAPCHANGEREQUIPMENT2) and assign them to the fields in the order to concatenate them.
TransformerUnit/TransformerUnit Object Class
Object class.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
CatalogID/CatalogID |
text |
|
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
RatedKVA |
long integer |
Transformer Unit KVA |
VoltageRegulatorBank/RegulatorBank
Simple Junction Feature that participates in the geometric network.
Field (Electric Distribution/MultiSpeak) |
Data Type |
Domain |
---|---|---|
ConsumptionType/ConsumptionType |
text |
Consumption Type |
*HighSideConfiguration |
text (length=5) |
Transformer Bank High Side Configuration (Default = D-D) |
HighSideProtection/PriProt |
text (length=5) |
Transformer Bank High Side Protection (Default = none) |
*LowSideConfiguration |
text (length=5) |
Transformer Bank Low Side Configuration (Default = D-D) |
Owner/Owner |
long integer |
Owner (Default = 1:Company) |
ElectricTraceWeight/ElectricTraceWeight |
long integer |
|
FacilityID/FacilityID |
text (length=20) |
|
FeederID/FeederID |
text (length=20) |
|
FeederID2/FeederID2 |
text (length=20) |
|
FeederInfo/FeederInfo |
long integer |
|
LowSideGroundResistance/ LowSideGroundResistance |
double |
|
OperatingVoltage/OperVolt |
long integer |
Electric Device Operating Voltage |
PhaseDesignation/PhasingCode |
long integer |
Phase Designation (no default value) |
Priority/Priority |
long integer |
Priority |
***TapChangerEquipment/TapChangerEquipment |
|
|
**WindingCode |
Text (length=50) |
Winding Code |
*The HighsideConfiguration and LowSideConfiguration fields are necessary only if you are using an Electric Distribution data model.
**The WindingCode field is necessary only if you are using a MultiSpeak data model.
*** You can have a single TapChangerEquipment field with the TAPCHANGEREQUIPMENT field model name assigned. Alternately, you can assign the field model name to multiple fields that are concatenated to create a single tap changer ID. For the fields to be concatenated in a specific order, add a numerical suffice to the field model names (e.g., TAPCHANGEREQUIPMENT1, TAPCHANGEREQUIPMENT2) and assign them to the fields in the order to concatenate them.