Feature class and field names are displayed as they appear in the standard data models (Electric Distribution/MultiSpeak).

All Classes

This applies to all network features or related unit tables including ConductorInfo. Note that all the tables listed below must have the MULTISPEAKCLASS model name assigned.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

PhaseDesignation/ PhasingCode

PhaseDesignation

MULTISPEAKFIELD

all connectivity objects and their units

msp:phaseCode

MS Data Type=text
Enumeration=msp:phaseCd
No default value

 

Network Feature Classes

This information applies to all network feature classes, including network junctions.

Note that if your data is configured for Feeder Manager 2.0, or if it's configured for both Feeder Manager 1.0 and 2.0, your feeder IDs populate the extensions.FeederID MS XML field from Feeder Manager 2.0's joined data, instead of from the FeederID and FeederID2 database fields.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

FacilityID/FacilityID

text

MULTISPEAKFIELD

facilityID

 

FeederID/FeederID

text

FEEDERID, MULTISPEAKEXTENSION, MULTISPEAKFIELD

connectivity objects

extensions.FeederID

Required for Feeder Manager and DMS export
MS Data Type=text
No default value

FeederID2/FeederID2

text

FEEDERID2

 

 

Required for Feeder Manager

ElectricTraceWeight/ ElectricTraceWeight

long int

MMELECTRICTRACEWEIGHT

 

 

Required for Feeder Manager

FeederInfo/FeederInfo

long int

FEEDERINFO

 

 

Required for Feeder Manager

 

All Unit Tables

This information applies to all Unit tables (e.g., ConductorInfo, TransformerUnit). The one exception is CapacitorUnit. MultiSpeak capacitors do not have an equipment field, so the CatalogID will be added to the extensions. See details below.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

CatalogID/CatalogID

text

MULTISPEAKEQUIPMENT

 

msp:eaEquipment

MS Data Type=text
No default value

 

BreakerUnit/DynamicProtectiveDeviceUnit

This feature class maps to msp:breaker in the MultiSpeak XML. The NormalPosition fields come from the parent (DynamicProtectiveDevice). If this table does not exist, then the phaseDesignation and CatalogID fields must be added to the CircuitSource table (see CircuitSource table, above).

 

BusBar

This feature class maps to msp:ugPrimaryLine in the MultiSpeak XML. The MultiSpeak data model does not have a BusBar feature class.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

Length/Length

(from geometry; not a field)

double

 

 

msp:condLength

MS Data Type=string

*NeutralSize/NeutSize

text

MULTISPEAKFIELD

msp:ugPrimaryLine

msp:condN

NeutralSize and NeutralMaterial are concatenated to produce msp:condN
MS Data Type=String

*NeutralMaterial/NeutType

text

MULTISPEAKFIELD

msp:ugPrimaryLine

OperatingVoltage/OperVolt

ElectricLineVoltage

OPERATINGVOLTAGE

 

 

Required for voltage validator

* Not in standard data model, but supported.

 

CapacitorUnit/CapacitorUnit

This feature class maps to msp:CapacitorUnit in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

CatalogID/CatalogID

text

MULTISPEAKEXTENSION

msp:Capacitor

msp:extensions/eaEquipment

MS Data Type=text
No default value

Kvar/Kvar

text

MULTISPEAKEQUIPMENT

msp:Capacitor

Capacitor KVAR

Use to create EquipmentID if CatalogID has no value.

 

CircuitSource/Source

This information applies to the CircuitSource table.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

ID/FeederID

string

FEEDERID, MULTISPEAKFIELD

msp:feederObject

msp:feederNo

MS Data Type=string

Name/FeederName

string

FEEDERNAME, MULTISPEAKFIELD

msp:feederObject

msp:feederName

MS Data Type=string
Enumeration=msp:phaseCd

ConnectionConfiguration/ ConnectionConfiguration

Circuit Source Connection Configuration

MULTISPEAKFIELD

msp:substation

msp:ldCon

Enumeration=msp:ldCon

SubstationID/ SubstationFacilityID

string

MULTISPEAKFIELD

msp:substation

msp:SubstationName

MS Data Type=string

*PhaseDesignation/PhasingCode and CatalogID are added only if a BreakerUnit does not exist.

PhaseDesignation/ PhasingCode

PhaseDesignation

MULTISPEAKFIELD

msp:breaker

msp:phaseCode

MS Data Type=text
Valid Values=msp:phaseCd
No default value

CatalogID/CatalogID

string

MULTISPEAKEQUIPMENT

msp:breaker

msp:eaEquipment

MS Data Type=text
No default value

 

ConductorInfo/ConductorInfo

This feature class maps to msp:conductor in the MultiSpeak XML. It contains only the following two fields: PhaseDesignation (All Classes) and catalogID (All Unit Tables).

 

DynamicProtectiveDevice/DynamicProtectiveDeviceBank

This feature class maps to msp:overcurrentDeviceBank in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

NormalPosition_A/PosA

Normal Status

NORMALPOSITION_A, MULTISPEAKFIELD

msp:overcurrentDeviceBank

msp:position

Enumeration=msp:position

NormalPosition_B/PosB

Normal Status

NORMALPOSITION_B, MULTISPEAKFIELD

msp:overcurrentDeviceBank

msp:position

Enumeration=msp:position

NormalPosition_C/PosC

Normal Status

NORMALPOSITION_C, MULTISPEAKFIELD

msp:overcurrentDeviceBank

msp:position

Enumeration=msp:position

SubtypeCD/SubtypeCode

long integer

MULTISPEAKFIELD

 

 

Use to create EquipmentID if CatalogID has no value.

MaxContinuousCurrent/ MaxContAmp

Over Current Prot Dev Max Continuous Current

MULTISPEAKFIELD

 

 

Use to create EquipmentID if CatalogID has no value.

ScadaControlID/ ScadaControlID

text

SCADACONTROLID

scadaPoint

objectID

 

SubstationID/SubstationID

text

SUBSTATIONID

msp:overcurrentDeviceBank

extensions.SUBSTATIONID

 

BayID/BayID

text

BAYID

msp:overcurrentDeviceBank

extensions.BAYID

 

 

Fuse/FuseBank

This feature class maps to msp:overcurrentDeviceBank in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

NormalPosition_A/PosA

Normal Status

NORMALPOSITION_A, MULTISPEAKFIELD

msp:overcurrentDeviceBank

msp:position

Enumeration=msp:position

NormalPosition_B/PosB

Normal Status

NORMALPOSITION_B, MULTISPEAKFIELD

msp:overcurrentDeviceBank

msp:position

Enumeration=msp:position

NormalPosition_C/PosC

Normal Status

NORMALPOSITION_C, MULTISPEAKFIELD

msp:overcurrentDeviceBank

msp:position

Enumeration=msp:position

SubstationID/SubstationID

text

SUBSTATIONID

msp:overcurrentDeviceBank

extensions.SUBSTATIONID

 

BayID/BayID

text

BAYID

msp:overcurrentDeviceBank

extensions.BAYID

 

 

FuseUnit/FuseUnit

This feature class maps to msp:fuse in the MultiSpeak XML. The NormalPosition fields come from the parent (Fuse).

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

LinkRating/LinkRtg

 long integer

MULTISPEAKFIELD

 

 

 

 

Use to create EquipmentID if CatalogID has no value.

LinkType/FuseType

 text

MULTISPEAKFIELD

 

 

 

 

Use to create EquipmentID if CatalogID has no value.

 

MiscNetworkFeature/MiscellaneousFeature

FaultIndicator features map to msp:outageDetectionDevice in the MultiSpeak XML. All other MiscNetworkFeatures are not exported.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

Direction/Direction

text

MULTISPEAKEXTENSION

 

extensions.DIRECTION

MS Data Type=text
Enumeration=FaultIndicatorDirection

SubtypeCD/SubtypeCode

long integer

MULTISPEAKFIELD

 

 

FaultIndicator only.

CatalogID/CatalogID

string

MULTISPEAKEQUIPMENT

 

extensions.eaEquipment

MS Data Type=text
No default value

 

PFCorrectingEquipment/CapacitorBank

This feature class maps to msp:CapacitorBank in the MultiSpeak XML. It contains only the following two fields: PhaseDesignation (All Classes) and FeederID (Network Feature Classes).

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

BankKvar/BankKvar

text

MULTISPEAKFIELD

BankKvar

msp:CapacitorBank

 

PriOHElectricLineSegment/PrimaryOHLineSection

This feature class maps to msp:ohPrimaryLine in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

*ConductorMaterial/CondMatl

text

MULTISPEAKFIELD

conductor

 

Used to create EquipmentID if CatalogID has no value.

*ConductorSize/CondSize

Conductor Size

MULTISPEAKFIELD

conductor

 

Used to create EquipmentID if CatalogID has no value.

*PhaseDesignation/ PhasingCode

PhaseDesignation

MULTISPEAKFIELD

all connectivity objects and their units

msp:phaseCode

MS Data Type=text
Enumeration=msp:phaseCd
No default value

Length/Length

(from geometry; not a field)

double

 

 

msp:condLength

MS Data Type=string

NeutralSize/NeutSize

text

MULTISPEAKFIELD

msp:ohPrimaryLine

msp:condN

NeutralSize and NeutralMaterial are concatenated to produce msp:condN
MS Data Type=String

NeutralMaterial/NeutType

text

MULTISPEAKFIELD

msp:ohPrimaryLine

OperatingVoltage/OperVolt

ElectricLineVoltage

OPERATINGVOLTAGE

 

 

Required for voltage validator

MeasuredLength

Numeric

MEASUREDLENGTH

msp:condLength

Optional. If this field is configured and populated it will be used as the conductor's length value. If not, Network Adapter uses the geometric shape length.

* These fields are necessary only if you do not have a ConductorInfo table. 

 

PriUGElectricLineSegment/PrimaryUGLineSection

This feature class maps to msp:ugPrimaryLine in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

Length/Length

(from geometry; not a field)

double

 

 

msp:condLength

MS Data Type=string

NeutralSize/NeutSize

text

MULTISPEAKFIELD

msp:ugPrimaryLine

msp:condN

NeutralSize and NeutralMaterial are concatenated to produce msp:condN
MS Data Type=String

NeutralMaterial/NeutType

text

MULTISPEAKFIELD

msp:ugPrimaryLine

OperatingVoltage/OPerVolt

ElectricLineVoltage

OPERATINGVOLTAGE

 

 

Required for voltage validator

MeasuredLength

Numeric

MEASUREDLENGTH

msp:condLength

Optional. If this field is configured and populated it will be used as the conductor's length value. If not, Network Adapter uses the geometric shape length.

 

RecloserUnit/DynamicProtectiveDeviceUnit

This feature class maps to msp:recloser in the MultiSpeak XML. The NormalPosition fields come from the parent (DynamicProtectiveDevice).

 

RegulatorUnit/RegulatorUnit

This feature class maps to msp:regulator and contains the fields displayed in the All Unit Tables section.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

RatedKVA/RatedKVA

Transformer Unit KVA

MULTISPEAKFIELD

 

 

Used to create EquipmentID if CatalogID has no value.

 

SectionalizerUnit/DynamicProtectiveDeviceUnit

This feature class maps to msp:sectionalizer in the MultiSpeak XML. The NormalPosition fields come from the parent (DynamicProtectiveDevice).

 

ServicePoint/ServiceLocation

This feature class maps to msp:serviceLocation in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Field

Notes

ConsumptionType/ ConsumptionType

text

MULTISPEAKEXTENSION

extensions.CONSUMPTIONTYPE

MS Data Type=text
Enumeration=consumption Type

 

Switch/SwitchBank

This feature class maps to msp:switchBank in the MultiSpeak XML. NormalPosition fields are stored on the SwitchBank, but exported to MultiSpeak as the SwitchUnit.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

NormalPosition_A/PosA

Normal Status

NORMALPOSITION_A, MULTISPEAKFIELD

msp:Switch

msp:position

Enumeration=msp:position

NormalPosition_B/PosB

Normal Status

NORMALPOSITION_B, MULTISPEAKFIELD

msp:Switch

msp:position

Enumeration=msp:position

NormalPosition_C/PosC

Normal Status

NORMALPOSITION_C, MULTISPEAKFIELD

msp:Switch

msp:position

Enumeration=msp:position

SubtypeCD/SubtypeCode

long integer

MULTISPEAKFIELD

 

 

Use to create EquipmentID if CatalogID has no value.

MaxContinuousCurrent/ MaxContAmp

 

MULTISPEAKFIELD

 

 

Use to create EquipmentID if CatalogID has no value.

ScadaControlID/ ScadaControlID

text

SCADACONTROLID

scadaPoint

objectID

 

SubstationID/SubstationID

text

SUBSTATIONID

msp:SwitchBank

extensions.SUBSTATIONID

 

BayID/BayID

text

BAYID

msp:SwitchBank

extensions.BAYID

 

 

SwitchingFacility/Substation

This feature class maps to msp:substation in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Field

Notes

SubstationID/SubstationID

text

SUBSTATIONID

extensions.SUBSTATIONID

 

 

SwitchUnit/SwitchUnit

This feature class maps to msp:switch in the MultiSpeak XML. The NormalPosition fields come from the parent feature class (SwitchBank).

 

Transformer/TransformerBank

This database table maps to the msp:transformerBank element in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Field

Notes

*HighSideConfiguration

TransformerBankHighSideConfiguration

HIGHSIDECONFIGURATION

msp:wdgCode

MS Data Type=string
Default=D-D
Enumeration=msp:wdgCode

*LowSideConfiguration

TransformerBankLowSideConfiguration

LOWSIDECONFIGURATION

HighSideProtection/PriProt

TransformerBankHighSideProtection

MULTISPEAKFIELD

msp:priProt

MS Data Type=string
Default="none"
Enumeration=highSide Protection

LowSideVoltage/SecVolt

long int

LOWSIDEVOLTAGE

msp:vOut

MS Data Type=float
Default value=20kV

LowSideGroundResistance/ LowSideGroundResistance

double

MULTISPEAKEXTENSION

lowSideGround

MS Data Type=float
Default value=20 ohm

FacilityID/FacilityID

string

MULTISPEAKFIELD

msp:facilityID

 

OperatingVoltage/OperVolt

ElectricDeviceOperatingVoltage

OPERATINGVOLTAGE

 

Required for voltage validation

ConsumptionType/ ConsumptionType

text

MULTISPEAKEXTENSION

extensions.consumptionType

MS Data Type=text
Enumeration=consumption Type

Owner/Owner

int
Domain=0:Other, 1:Company

MULTISPEAKEXTENSION

owner

MS Data Type=int
Default value=1

Priority/Priority

int

MULTISPEAKEXTENSION

priority

MS Data Type=int

*WindingCode

Winding Code

MULTISPEAKFIELD

 

In the MultiSpeak data model, this field replaces HighSideConfiguration and LowSideConfiguration.

* HighSideConfiguration and LowSideConfiguration together, are mapped to Multispeak's wdgCode 

 

TransformerUnit/TransformerUnit

This feature class maps to msp:transformer and contains the fields displayed in the All Unit Tables section.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Element

MS XML Field

Notes

RatedKVA/RatedKVA

Transformer Unit KVA

MULTISPEAKFIELD

 

 

Used to create EquipmentID if CatalogID has no value.

 

VoltageRegulator/RegulatorBank

This database table maps to the msp:transformerBank element in the MultiSpeak XML.

Database Field (Electric Distribution/MultiSpeak)

Field Type/Domain

Model Names

MS XML Field

Notes

*HighSideConfiguration

TransformerBankHighSideConfiguration

HIGHSIDECONFIGURATION

msp:wdgCode

MS Data Type=string
Default=D-D
Enumeration=msp:wdgCode

*LowSideConfiguration

TransformerBankLowSideConfiguration

LOWSIDECONFIGURATION

HighSideProtection/PriProt

TransformerBankHighSideProtection

MULTISPEAKFIELD

msp:priProt

MS Data Type=string
Default="none"
Enumeration=highSide Protection

LowSideVoltage/SecVolt

long int

LOWSIDEVOLTAGE

msp:vOut

MS Data Type=float
Default value=20kV

LowSideGroundResistance/ LowSideGroundResistance

double

MULTISPEAKEXTENSION

lowSideGround

MS Data Type=float
Default value=20 ohm

FacilityID/FacilityID

string

MULTISPEAKFIELD

msp:facilityID

 

OperatingVoltage/OperVolt

ElectricDeviceOperatingVoltage

OPERATINGVOLTAGE

 

Required for voltage validation

ConsumptionType/ ConsumptionType

text

MULTISPEAKEXTENSION

extensions.consumptionType

MS Data Type=text
Enumeration=consumption Type

Owner/Owner

int
Domain=0:Other, 1:Company

MULTISPEAKEXTENSION

owner

MS Data Type=int
Default value=1

Priority/Priority

int

MULTISPEAKEXTENSION

priority

MS Data Type=int

**TapChangerEquipment/ TapChangerEquipment

 

TAPCHANGEREQUIPMENT

 

 

*WindingCode

Winding Code

MULTISPEAKFIELD

 

In the MultiSpeak data model, this field replaces HighSideConfiguration and LowSideConfiguration.

* HighSideConfiguration and LowSideConfiguration together, are mapped to Multispeak's wdgCode

** You can have a single TapChangerEquipment field with the TAPCHANGEREQUIPMENT field model name assigned. Alternately, you can assign the field model name to multiple fields that are concatenated to create a single tap changer ID. For the fields to be concatenated in a specific order, add a numerical suffice to the field model names (e.g., TAPCHANGEREQUIPMENT_1, TAPCHANGEREQUIPMENT_2) and assign them to the fields in the order to concatenate them.  

 

 

 