A circuit (feeder) is the aggregate of the conductors and equipment downstream of a substation breaker or recloser. CircuitSource stores attributes that describe characteristics of the circuit measured or estimated at the breaker or recloser. These attributes include capacity, measured in kilowatts (kW); resistance, measured in ohms; and load, measured in reactive kilovolt-amperes (kVAR).
Associations: BusBar, CircuitBreaker, Recloser
Subtypes: kW, Swing, Voltage Controlled. The use of subtypes is optional. The Subtype attribute can be removed if subtypes aren't used in the model.
Model Names: CIRCUITSOURCE
Attributes:
BusBarObjectID: long integer - ObjectID of associated BusBar.
ConnectionConfiguration: text - Code indicating configuration of conductors; domain values include Delta, Wye, etc.
DynamicProtectiveDevObjectID: long integer - ObjectID of associated dynamic protective device.
EmergencyCapacitykW: long integer - Emergency rating of CircuitSource, in KW; domain values include 12.
FeederSourceInfo: long integer - Stores information about source of feeder. Feeder Manager requires the FEEDERSOURCEINFO model name on this field. Feeder Manager uses this field to determine whether a feeder has features that participate either loop or multifeed situations.
GroundReactance: double - Reactance of ground seen at the source by the downstream circuit.
GroundResistence: double - Resistance of ground seen at the source by the downstream circuit.
Hyperlink: text - Used to store a hyperlink path via standard Esri hyperlinking functionality.
ID: text - System-generated identifier of feeder initiated at this source. Feeder Manager uses the FEEDERID model name on this field.
MaximumCapacitykW: long integer - Maximum allowable operating capacity of CircuitSource; domain values include 10.
MaxKVAR: long integer - Maximum kVAR load experienced at CircuitSource; domain values include 6.
MaxPositiveSequenceReactance: double - Maximum positive sequence reactance seen at the source by the downstream circuit in ohms.
MaxPositiveSequenceResistance: double - Maximum positive sequence resistance seen at the source by the downstream circuit in ohms.
MaxZeroSequenceReactance: double - Maximum zero sequence reactance seen at the source by the downstream circuit in ohms.
MaxZeroSequenceResistance: double - Maximum zero sequence resistance seen at the source by the downstream circuit in ohms.
MinFaultCurrentOH: long integer - Calculated minimum fault current for overhead conductors.
MinFaultCurrentUG: long integer - Calculated minimum fault current for underground conductors.
MinkVAR: long integer - Minimum kVAR load experienced at CircuitSource; domain values include 500, etc.
MinPositiveSequenceReactance: double - Minimum positive sequence reactance seen at the source by the downstream circuit in ohms.
MinPositiveSequenceResistance: double - Minimum positive sequence resistance seen at the source by the downstream circuit in ohms.
MinZeroSequenceReactance: double - Minimum zero sequence reactance seen at the source by the downstream circuit in ohms.
MinZeroSequenceResistance: double - Minimum zero sequence resistance seen at the source by the downstream circuit in ohms.
Name: text - Utility name of CircuitSource. Feeder Manager uses the FEEDERNAME model name on this field.
NominalVoltage: long integer - Code indicating system voltage for which CircuitSource is rated; domain values include 7.2 kV Grounded Y, 24.9 kV Grounded Y, 2400 Delta, etc.
OperatingVoltage: long integer - Code indicating standard level of voltage at which system is currently operated in kV; domain values include 12.5 kV Grounded Y, 7.2 kV Grounded Y, etc.
SubstationID: text - Substation identifier. Feeder Manager uses the SUBSTATIONID model name on this field to identify the substation that acts as a source.
VoltageAngle: double - Angle at which phase is offset from system standard.